of the follower clamp (3). It must rest on
it with spring force.
Screw tight the mounting plate (21) onto
the actuator yoke using both fixing
screws.
7. Mount cover (11) on the other side.
Make sure that the vent plug points
downwards when the control valve is in
-
stalled to allow any condensed water
that collects to drain off.
4.7.2 Mounting the position
sensor with attachment
according to IEC 60534-6
For the required mounting parts and the ac
-
cessories, refer to Table 7 on page 46.
1. Place the lever (1) on the sensor in
mid-position and hold it in place.
Unthread the nut (1.1) and remove the
lever together with the disk spring (1.2)
from the sensor shaft.
2. Screw the position sensor (20) onto the
bracket (21).
The standard attached lever M with the fol
-
lower pin (2) at position 35 is designed for
120, 240 and 350 cm² actuators with
15 mm rated travel.
For other actuator sizes or travels, select the
lever and pin position from the travel table
on page 15. Lever L and XL are included in
the mounting kit.
3. Place the lever (1) and disk spring (1.2)
on the sensor shaft. Place the lever (1) in
mid-position and hold it in place. Screw
on the nut (1.1).
4. Screw both bolts (14) to the bracket
(9.1) of the stem connector (9). Attach
38 EB 8384-4 EN
Attachment to the control valve – Mounting parts and accessories
20 21
2
1.1, 1.2 14.1 3 14 99.1
Fig. 18 · Mounting according to IEC 60534-6 (NAMUR)
1 Lever
1.1 Nut
1.2 Disk spring
2 Follower pin
3 Follower plate
9 Stem connector
9.1 Bracket
14 Bolt
14.1 Screws
20 Position sensor
21 Bracket