Samson 3730 Series Bedienungsanleitung Seite 5

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 8
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 4
5 T 8384-6 EN
Summary of explosion protection certificates
Type of approval Certificate number Date Type of protection/Comments
EC Type Examination Certificate PTB 10 ATEX 2007 2010-08-18 II 2 G Ex ia IIC/IIB T6; Type 3730-6-110/-210
II 2G Ex d [ia] IIC/IIB T6; with Type 3770 Field Barrier
II 2 D Ex tD A21 IP 6 T 80 °C
Statement of Conformity PTB 10 ATEX 2008 X 2010-08-18 II 3 G Ex nA II T6; Zone 2; Type 3730-6-810
II 3G Ex nL IIC/IIB T6
II 3D Ex tD A22 IP 66 T 80 °C; Zone 22 dust
IECEx IECEx PTB 10.0057 2010-12-10 Ex ia IIC/IIB T6 and Ex tD A21 IP66 T 80 °C; Type 3730-6-111
Ex d[ia] IIC/IIB T6 and Ex tD A21 IP66 T 80 °C; Type 3730-6-211
IECEx PTB 10.0058X 2010-12-10 Ex nA II T6 or Ex nL IIC/IIB T6 or
Ex tD A22 IP66 T 80 °C; Type 3730-6-811
GOST approval B 03115 2010-09-27 1 Ex ia IIC T4...T6 X / DIP A21 T
A
80 °C
Ex nA II / Ex nL IIC T4...T6 X / DIP A22 T
A
80 °C;
Valid until 2013-09-27
The test certificates are included in the mounting and operating instructions or are available on request.
Refer to Data Sheet T 8379 EN for EEx d certificates for the Type 3770 Field Barrier.
External position sensor
Travel Same as positioner
Cable 10 m · Flexible and durable · With M12x1 connector · Flame-retardant acc. to VDE 0472
Resistant to oils, lubricants and coolants as well as other aggressive media
Permissible ambient temperature –60 to +105 °C · The limits in the test certificate additionally apply for explosion-protected devices.
Immunity to vibration Up to 10 g in the range of 10 to 2000 Hz
Degree of protection IP 67
Binary input · Electrical isolation · Switching behavior configured over software
Active switching behavior (default setting)
Connection For external switch (floating contact) or relay contact
Electrical data
Open-circuit voltage when contact is open: 10 V
Pulsed DC current reaching peak value of 100 mA and RMS value of 0.01 mA when contact is closed
Contact
Closed, R < 20
W
“On” switching state (default setting)
Open, R > 400
W
“Off” switching state (default setting)
Passive switching behavior
Connection For externally applied DC voltage, reverse polarity protection
Electrical data 3 to 30 V · Destruction limit 40 V · Current draw 3.7 mA at 24 V
Voltage
> 6 V “On” switching state (default setting)
< 1 V “Off” switching state (default setting)
Seitenansicht 4