Solenoid valve (forced venting function)
For positioners fitted with the optional sole
-
noid valve for the forced venting function, a
voltage of 24 V DC must be connected to
the relevant terminals +81 and –82.
NOTICE
If there is no voltage connected for the sole
-
noid valve at terminals +81 and –82 or
when the voltage signal is interrupted, the
positioner vents the actuator and does not
respond to the set point.
Observe the switching thresholds specified
in the technical data.
5.2.1 Establishing communication
The communication structure between the
controller, logic solvers (PLC) or automation
system, or between a PC or work station
and the positioner(s) is implemented by a
segment coupler (see Fig. 22) conforming to
PROFIBUS directives.
Explosion-protected versions of
PROFIBUS-PA segment couplers must be
used in hazardous areas.
A maximum of 32 positioners may be oper
-
ated in parallel over a segment coupler in
one PROFIBUS-PA segment. In hazardous
areas, the number of positioners that can be
connected is reduced.
Each positioner connected in the segment
must be assigned a unique bus address be-
tween 0 and 125 (refer to section 7.10).
EB 8384-4 EN 51
Connections