Samson S2000 Betriebsanleitung Seite 62

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 124
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 61
Turn
Code 3, display: No
Press
Code 3 blinks
Turn
YES
Press , display
Select the initialization mode:
Initialization mode
Default
MAX
Turn
Code 6
Press
Turn
MAX
Press to confirm the MAX as the initial-
ization mode.
Start initialization:
4
Press INIT key to start initialization!
The nominal travel/angle of rotation is indi
-
cated in % after initialization. Code
5 (nomi
-
nal range) remains locked. The parameters
for travel/angle range start (Code
8) and
travel/angle range end (Code 9) can also
only be displayed and modified in %.
For a reading in mm/°, enter the pin posi
-
tion (Code
4).
Enter the pin position:
Pin position
Default
No
Turn
Code 4
Press , Code 4 blinks
Turn
Pin position on lever (see rele
-
vant section on attachment)
Press . The reading of the nominal range
appears in mm/°.
7.6.2 NOM – Initialization based
on nominal range
The calibrated sensor allows the effective
valve travel to be set very accurately. During
the initialization process, the positioner
checks whether the control valve can move
through the indicated nominal range (travel
or angle) without collision.
If this is the case, the indicated nominal
range is adopted with the limits of
travel/angle range start (Code 8) and
travel/angle range end (Code 9) as the op
-
erating range.
Note: The maximum possible travel must al
-
ways be greater than the nominal travel en
-
tered. If this is not the case, initialization is
interrupted (error alarm Code 52) because
the nominal travel is not achieved.
62 EB 8384-4 EN
Start-up Settings
mm
Seitenansicht 61
1 2 ... 57 58 59 60 61 62 63 64 65 66 67 ... 123 124

Kommentare zu diesen Handbüchern

Keine Kommentare