7.6 Initialization
WARNING!
During initialization, the control valve moves
through its entire travel/angle of rotation
range. Therefore, do not start the initializa
-
tion procedure while a process is running,
but only during start-up when all shut-off
valves are closed.
Before starting initialization, check the maxi
-
mum permissible signal pressure of the con
-
trol valve. During initialization, the
positioner issues an output signal pressure
up to the maximum supply pressure sup
-
plied. If necessary, limit the signal pressure
by connecting an upstream pressure reduc-
ing valve.
NOTICE
After the positioner has been mounted on to
another actuator or its mounting location
has been changed and prior to
re-initializing the positioner, the positioner
needs to be reset to its basic setting (default
values). Refer to section 7.8.
During initialization the positioner adapts it
-
self optimally to the friction conditions and
the signal pressure demand of the control
valve. The type and extent of self-adaptation
depends on the set initialization mode:
4
MAX maximum range (standard range)
Initialization mode for simple start-up of
valves with two clearly defined mechani
-
cal end positions, e.g. three-way valves
(see section 7.6.1)
4
NOM nominal range
Initialization mode for all globe valves
(see section 7.6.2)
4
MAN manually selected range
Initialization mode for globe valves with
an unknown nominal range (see section
7.6.3)
4
SUb substitute calibration (emergency
mode)
This mode allows a positioner to be re
-
placed while the plant is running, with
the least amount of disruption to the
plant (see section 7.6.4)
Note: For normal operation, simply start ini
-
tialization by pressing the INIT key after
mounting the positioner on the valve and
defining the valve closed position and set-
ting the volume restriction. The positioner
only needs to work with its default settings. If
necessary, perform a reset (see section 7.8).
Alternating displays
Initialization running
Symbol depending on ini
-
tialization mode selected
Bar graph display
indicating the progress of
the initialization
Initialization successful,
positioner in automatic
operating mode
60 EB 8384-4 EN
Start-up Settings
%